INPUT
TYPE (INPT)
Refer to Table 23-1 for a summary list of menu configuration.
To select your appropriate input type signal.
1. Press the MENU button until the meter shows "INPT"
2. Press the /DEV
button. The meter shows one of the following:
* J.TC - Iron
vs. Constantan (NIST)
* K.TC - Nickel-Chromium vs. Nickel-Aluminum (NIST)
* DJ.TC - Iron vs. Copper (DIN) * K.TC - Nickel-Chromium
vs. Nickel-Aluminum (NIST)
* T.TC - Copper vs. Copper-Nickel
3. Press the
/MAX button
to scroll between available choices.
4. Press the MENU button to store your selection. The meter
momentarily shows "STRD", followed by "DEC.P" (Decimal point).
To
select a decimal point display position
1. Press the MENU button. The meter shows ""DEC.P".".
2. Press the /DEV
button.
The meter flashes one of the following:
* FFFF.
* FFF.F
3. Press the /MAX
button to scroll through available choices.
4. Press the MENU button to store your selection.
The meter momentarily shows "STRD", followed by "RD.CF"
(Reading Configuration).
When you change the decimal position the meter adjusts setpoints, deadbands,
proportional band, and manual reset values. These adjustments are made
according to the new decimal point. If one or more of these values overflow
the meter flashes "ER2" when you store a new decimal point position value.
AUTOMATIC
DECIMAL POINT ADJUST
If you select 0.1 degree resolution the decimal point automatically adjusts
itself to 1 degree if the temperature reading is above 999.9 or below
-199.9.
READING
CONFIGURATION ("RD.CF")
READING CONFIGURATION ("RD.CF")
To determine if your meter shows in ░F (Fahrenheit)
or ░C (Celsius).
1. Press the MENU button until "RD.CF" displays.
2. Press the /DEV
button.
The meter shows one of the following:
* "R.1=F" (░F)
* "R.1=C" (░C)
3. Press the /MAX
button to toggle between choices.
4. press the MENU
button to store your selection. The
meter momentarily shows "STRD", followed by "S1.CF" (Setpoint
1 Configuration).
SETPOINT
1 CONFIGURATION
Setpoint 1
is not active unless your meter has dual relay output capabilities. The
LED's will display whether the (S1.CF) is active or not. You may
use Setpoint 1 Configuration (S1.CF) for the following:
* To Set setpoint's
active band above or below your chosen value
* To Set whether the setpoint operation is latched or unlatched
1. Press the
MENU button until the meter shows "S1.CF".
2. Press the /DEV
button. The meter shows one of the following:
* "S.1=A"
(Active above the setpoint)
* "S.1=B" (Active below the setpoint)
3. Press the
/MAX button
to toggle between choices.
4. Press the /DEV
button again. The meter shows one of the following:
* "S.2=L"
(setpoint 1 to be latched)
* "S.2=U" (setpoint 1 to be unlatched)
5. Press the
/MAX button
to toggle between choices.
6.
Press the MENU button to store your selection(s). The meter momentarily
shows "STRD", followed by "S2.CF" (Setpoint 2 Configuration).
|